Fire separation between factory buildings and warehouses
Fire separation between factory buildings and warehouses
In the Code of Design on Building Fire Protection and Prevention, the fire prevention distance between the workshop has been clearly stipulated: the fire prevention distance between the workshop and b, c, d, e warehouses and civil buildings should not be less than the following table.
Table: fire prevention distance between workshops and class b, c, d, e warehouses and civil buildings (m)
Note: 1 fire prevention distance between class b workshop and important public buildings should not be less than 50m;Place with open fire or spark, not less than 30m.Fire prevention distance between single and multi-storey class e factory buildings and with class e warehouse can be reduced by 2m according to the provisions of this table. Fire prevention distance between class e factory buildings and civil buildings can be equivalent to civil buildings according to the provisions of article 5.2.2 of this code.For c, d, e plant services and separate set of living room should be determined according to civil buildings, and the fire prevention distance with the plant should not be less than 6m.When really need adjacent arrangement, should accord with the regulation of note 2, 3 of this table.
2. If the higher outer wall adjacent to the two workshops is a firewall, or if the fire resistance limit of the roof is not less than 1.00h and the outer wall of either side of the adjacent buildings of the same height of the first and second fire-resistant buildings is a firewall, the fire prevention distance is not limited, but the first class workshops should not be less than 4m.The two adjacent outer walls of the two c, d and e plant are non-combustible walls. When there is no exposed combustible eaves, the sum of the area of doors, Windows and openings on each outer wall shall not be greater than 5% of the area of the outer wall, and the fire spacing shall be reduced by 25% according to the provisions of this table.Class a and b plant (warehouse) shall not be adjacent to other buildings other than those specified in article 3.3.5 of this code.
3 two, the level of secondary refractory plant, when the lower side wall adjacent to the firewall and lower a workshop roof skylight, the fire resistance of the roof is not less than 1.00 h, or high side wall adjacent open parts such as door, window set of class a fire door, window, or fire separation water curtain or according to the provisions of this standard article 6.5.3 set fire shutter, fire separation between party a and b plant should not be less than 6 m;The fire prevention distance between c, d and e plants should not be less than 4m.
Oil quantity of main transformer in power plant can be determined by single transformer.
If the fire resistance rating is lower than grade 4, the fire resistance rating of the existing plant can be determined according to grade 4.
6 if the c, d and e plant is adjacent to the c, d and e warehouse, it shall comply with the provisions of note 2 and 3 of this table.
The fire prevention distance between class a warehouses and other buildings, open fire or spark emitting places, railways and roads shall not be less than the following table.
Table: a class between warehouse and other buildings, open flames, or sending out spark locations, such as railways, roads, fire prevention spacing (m) note: class a fire separation between warehouse, when items 3 and 4 reserves is not more than 2 t, 1, 2, 5, 6 items reserves is not greater than 5 t, shall not be less than 12 m, with top class a warehouse warehouse fire prevention spacing should be not less than 13 m.
Table: fire prevention distance between b, c, d and e warehouses and civil buildings
We can find some patterns from several tables:
1. The fire prevention distance between class a and class b workshops, warehouses and single multi-storey buildings and skirt houses in civil buildings is 25m, and the fire prevention distance between them and high-rise civil buildings is 50m.(category a warehouse is special and needs to consider the category of storage items)
2. The fire prevention distance between single-storey, multi-storey and high-rise class a and b workshops and outdoor substation is 25m.
3. In addition to class a warehouse and outdoor transformer power station, the fire prevention distance between workshop warehouse and civil buildings can be calculated according to the following formula:
D = L + N1 + N2
L (type) value: 13 meters for high-rise workshop warehouse, 12 meters for class a workshop warehouse, and 10 meters for others
Value: 1, 2, 3, 4
The fire spacing between the factory and the warehouse is easily confused. The main differences between the two are:
Workshop:
If the outer wall of the higher adjacent side of the two workshops is a firewall, or if the outer wall of the adjacent side of the building of the same height of the first and second fire resistant grade is a firewall and the fire resistance limit of the roof is not less than 1.00h, the fire prevention distance is not limited, but the first class workshops should not be less than 4m.
C, d, e plant and civil building fire rating are one, two, when the higher one side of the wall is no door, window, hole firewall, or than adjacent lower a building roof high 15m and the following range of external walls are no door, window, hole firewall, its fire spacing is not limited.
First and second class of refractory grade two plants, when the lower side wall adjacent to the firewall and lower a workshop roof skylight, the fire resistance of the roof is not less than 1.00 h, or high side wall adjacent open parts such as door, window set of class a fire door, window, or fire separation water curtain or according to the provisions of this standard article 6.5.3 set fire shutter, fire separation between party a and b plant should not be less than 6 m;The fire prevention distance between c, d and e plants should not be less than 4m.
When the fire resistance grade of class c, d and e factory buildings and civil buildings is grade 1 or 2, the adjacent lower outer wall is the firewall, and the roof has no skylight or hole, the fire resistance limit of the roof is no less than 1.00h, or the higher adjacent wall is the firewall, and fire prevention measures have been taken on the opening part of the wall, the fire prevention distance can be appropriately reduced, but should not be less than 4m.
The fire prevention distance between single and multi-storey class e factories and with class e warehouses can be reduced by 2m according to table 3.4.1. The fire prevention distance between class e factories and civil buildings can be equivalent to civil buildings according to article 5.2.2 of this code.For c, d, e plant services and separate set of living room should be determined according to civil buildings, and the fire prevention distance with the plant should not be less than 6m.
The fire prevention distance between the class a workshop and important public buildings should not be less than 50m, and the fire prevention distance between the open fire or spark emitting places should not be less than 30m.
Warehouse:
When the adjacent external walls of the two warehouses are firewalls, the fire spacing can be reduced, but the type c warehouse, should not be less than 6m;D and e warehouses should not be less than 4m.
Two adjacent higher warehouse side walls for firewall, or between two highly rated the same first and second level building in adjacent either side walls for the firewall and the fire resistance of the roof is not lower than 1.00 h, and the total area is not more than this specification article 3.3.2 rainfall distribution on 10-12 maximum allowable covers an area of a warehouse regulations, its fire prevention spacing is unlimited.
D, e class warehouse and civil building fire rating are a, two, when the higher one side of the wall is no door, window, hole firewall, or than adjacent lower a building roof height of 15m and the following range of external wall is no door, window, hole firewall, its fire spacing is not limited.
Butyl, amyl warehouse and civil construction of refractory are one, second class, lower side wall adjacent to the firewall, and roof skylight or the mouth of the cave, fireproof limit not less than 1.00 h, or high side wall adjacent to the firewall, and wall openings site fire prevention measures were taken, the fire separation can be appropriately reduced, but should not be less than 4 m.
The fire prevention distance between single and multi-storey e warehouses can be reduced by 2m according to table 3.5.2.
Except for item 6 of category b, the fire prevention distance between category b warehouse and civil buildings should not be less than 25m, the fire prevention distance between important public buildings should not be less than 50m, and the fire prevention distance between category a warehouse and railway and road should not be less than the fire prevention distance between category a warehouse and railway and road in table 3.5.1.